Indicate on the diagrams the factored loads that stress the indicated beams
Description
Figure 3 shows a plan view of a reinforced concrete floor supported by steel beams. The factored loads for the beams shown in Figures 3.1 to 3.6 on the next page are requested (also indicate the span of each beam).
The unweighted loads in kPa (kN/m2) uniformly distributed over the slab are :
– Weight of the slab : 4,80
– 40 mm terrazzo finish: 1.00
– Suspended ceiling: 0.15
– Ventilation, plumbing, electricity, etc.: 0.25
– Partitions: 1.00
– Live load: 2.40